Mold Inspection Consulting and Remediation Organization
Since 2006
close menu

Fluke 922 Airflow Meter / Micromanometer

The Fluke 922 Airflow Meter was designed and built for how (and where) you do your job, with performance, ruggedness and ease of use, setting it apart from the competition.

More info

Fluke 922 Airflow Meter / Micromanometer
Roll over image to zoom Click image to expand
  • Fluke 922 Airflow Meter / Micromanometer

The Fluke 922 Airflow Meter was designed and built for how (and where) you do your job, with performance, ruggedness and ease of use, setting it apart from the competition. The bright white display and ruggedized holster and wrist strap let you take the Fluke 922 micromanometer into less than ideal environments.

The color-coded hoses help you keep track of where your readings are coming from. The simple, intuitive interface means you can measure pressure, velocity, or airflow at the push of a button. The Fluke 922 Airflow Meter helps you analyze airflow easily.

Features:

  • Powerful meter provides differential and static pressure, air velocity and flow readings
  • Convenient colored hoses help proper interpretation of pressure readings
  • Easy to use without sacrificing performance
  • Bright, backlit display for clear viewing in all environments
  • User-defined duct shape and size for maximum airflow accuracy
  • Resolution down to 0.001 inH2O
  • 99 point data storage capacity
  • Min/Max/Average/Hold functions for easy data analysis
  • Auto power off saves battery life
Technical Specifications
Air pressure Range / Resolution / Accuracy ±4000 Pascals / 1 Pascal / ±1% + 1 Pascal
±16 inH2O / 0.001 inH2O / ±1% + 0.01 inH2O
±400 mmH2O / 0.1 mmH2O / ±1% + 0.1 mmH2O
±40 mbar / 0.01 mbar / ±1% + 0.01 mbar
±0.6 psi / 0.0001 psi / ±1% + 0.0001 psi
Air velocity Range / Resolution / Accuracy 250 to 16,000 fpm / 1 fpm / ±2.5% of reading at 2000 fpm (10.00 m/s)
1 to 80 m/s / 0.001 m/s / ±2.5% of reading at 2000 fpm (10.00 m/s)
Air flow (volume) Range / Resolution / Accuracy 0 to 99,999 cfm / 1 cfm / Accuracy is a function of velocity and duct size
0 to 99,999 / 1 m3/hr / Accuracy is a function of velocity and duct size
0 to 99,999 l/s / 1 l/s / Accuracy is a function of velocity and duct size
Temperature Range / Resolution / Accuracy 0°C to 50°C / ±1% + 2°C / 0.1°C
32°F to 122°F / ±1% + 4°F / 0.1°F
General Specifications
Operating temperature 0°C to +50°C (+32°F to +122°F)
Storage temperature -40°C to +60°C (-40°F to +140°F)
Relative humidity 0% to 90%, non-condensing
IP rating IP40
Operating altitude 2000 m
Storage altitude 12000 m
EMI, RFI, EMC Meets requirements for EN61326-1
Vibration MIL-PREF-28800F, Class 3
Max pressure at each port 10 psi
Data storage capacity 99 readings
Warranty 2 years
Power, battery life Four AA batteries
Battery life 280 hours without backlight, 60 hours with backlight