Mold Inspection Consulting and Remediation Organization
Since 2006
close menu

Fluke 1507 Insulation Resistance Tester

The Fluke 1507 is a versatile, compact, handheld insulation tester for advanced industrial and electrical insulation testing.

More info

Fluke 1507 Insulation Resistance Tester
Roll over image to zoom Click image to expand
  • Fluke 1507 Insulation Resistance Tester

The Fluke 1507 is a versatile, compact, handheld insulation tester for advanced industrial and electrical insulation testing. Its multiple test voltages make it the ideal tool for many troubleshooting, commissioning, and preventative maintenance applications.

Take advantage of the 1507 full feature set to easily and quickly perform advanced insulation resistance testing. Its handy size and light weight make it easy to pack and use. Additional features, like the remote probe, save both time and money especially when performing repetitive tests. And its reasonable price and rugged reliability make it an excellent value.

Capabilities:

  • Performs insulation tests from 0.01 MΩ to 10 GΩ
  • Includes live circuit detection to prevent insulation test if voltage >30 V is detected
  • Includes auto-discharge of capacitive voltage for added user protection
  • Measures AC/DC voltage from 0.1 V to 600 V and resistance from 0.01 Ω to 20.00 kΩ
  • Provides lo-ohms earth-bond continuity (200 mA)
  • Simplifies repetitive or hard-to-reach testing with the remote test probe
  • Saves battery power with auto power off
  • Presents results on a large, backlit display
  • Features CAT IV 600 V overvoltage category rating
  • Comes with remote probe, test leads, test probes, alligator clips and one-year warranty
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Runs on four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests

Specifications:

AC/DC Voltage Measurement
Accuracy Range 600.0 V
Resolution 0.1 V
50 Hz to 400 Hz ± (% of Rdg + Digits) ±(2% + 3)
Input impedance 3 MΩ (nominal), < 100 pF
Common mode rejection ratio (1 kΩ unbalanced): > 60 dB at DC, 50 or 60 Hz
Overload protection 600 V rms or DC
Earth Bond Resistance Measurement
Range/Resolution 20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ
Accuracy ±(1.5% + 3)
Overload protection 2 V rms or DC
Open circuit test voltage > 4.0 V, < 8 V
Short circuit current > 200.0 mA
Insulation Specifications
Measurement range 0.01 MΩ to 10 GΩ
Test voltage 50 V, 100 V, 250 V, 500 V, 1000 V
Test voltage accuracy + 20%, - 0%
Short circuit current 1 mA nominal
Auto discharge Discharge time < 0.5 second for C = 1 µF or less
Live circuit indicator Inhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive load Operable with up to 1 µF load
Measure accuracy 50 V ±(3% + 5)
100 V ±(3% + 5)
250 V ±(1.5% + 5)
500 V ±(1.5% + 5)
1000 V ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ
General Specifications
Maximum voltage applied to any terminal: 600 V AC rms or DC
Storage temperature -40°C to 60°C (-40°F to 140°F)
Operating temperature -20°C to 55°C (-4°F to 131°F)
Temperature coefficient 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F)
Relative humidity
0% to 95% @ 10°C to 30°C (50°F to 86°F)
0% to 75% @ 30°C to 40°C (86°F to 104°F)
0% to 40% @ 40°C to 55°C (104°F to 131°F)
Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Shock 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
Electromagnetic compatibility In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
Safety Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
Certifications CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
Batteries Four AA batteries (NEDA 15A or IEC LR6)
Battery life Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L) 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight 550 g (1.2 lb)
IP rating IP40
Altitude Operating 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage) 12,000 m
Over-range capability 110% of range
Included accessories TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe