Specifications |
AC Current via Jaw |
Range |
999.9 A |
Resolution |
0.1 A |
Accuracy |
2% ± 5 digits (10-100 Hz) 5% ± 5 digits (100-500 Hz) |
Crest Factor (50/60 Hz) |
3 @ 500 A 2.5 @ 600 A 1.42 @ 1000 A Add 2% for C.F. > 2 |
AC Current via Flexible Current Probe |
Range |
999.9 A / 2500 A (45 Hz – 500 Hz) |
Resolution |
0.1 A / 1 A |
Accuracy |
3% ± 5 digits |
Crest Factor (50/60 Hz) |
3.0 at 1100 A 2.5 at 1400 A 1.42 at 2500 A Add 2% for C.F. > 2 |
Position Sensitivity |
|
Distance from Optimum |
|
i2500-10 Flex |
i2500-18 Flex |
Error |
A |
0.5 in (12.7 mm) |
1.4 in (35.6 mm) |
±0.5% |
B |
0.8 in (20.3 mm) |
2.0 in (50.8 mm) |
±1.0% |
C |
1.4 in (35.6 mm) |
2.5 in (63.5 mm) |
±2.0% |
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. |
DC Current |
Range |
999.9 A |
Resolution |
0.1 A |
Accuracy |
2% ± 5 digits |
AC Voltage |
Range |
600 V /1000 V |
Resolution |
0.1 V / 1 V |
Accuracy |
1.5% ± 5 digits (20 – 500 Hz) |
DC Voltage |
Range |
600.0 V /1000 V |
Resolution |
0.1 V / 1 V |
Accuracy |
1% ± 5 digits |
Frequency – Via Jaw |
Range |
5.0 – 500.0 Hz |
Resolution |
0.1 Hz |
Accuracy |
0.5% ± 5 digits |
Trigger Level |
5 – 10 Hz, ≥ 10 A 10 – 100 Hz, ≥ 5 A 100 – 500 Hz, ≥ 10 A |
Frequency via Flexible Current Probe |
Range |
5.0 to 500.0 Hz |
Resolution |
0.1 Hz |
Accuracy |
0.5% ± 5 digits |
Trigger Level |
5 to 20 Hz, ≥ 25 A 20 to 100 Hz, ≥ 20 A 100 to 500 Hz, ≥ 25 A |
Resistance |
Range |
600 Ω/6 kΩ/60 kΩ |
Resolution |
0.1 Ω/1 Ω/10 Ω |
Accuracy |
1% ± 5 digits |
Mechanical Specifications |
Size (L x W x H) |
277 x 88 x 43 mm (55 mm for remote unit) |
Weight |
350 g |
Jaw Opening |
34 mm |
Flexible Current Probe Diameter |
7.5 mm |
Flexible Current Probe Cable Length (head to electronics connector) |
1.8 m |
Environmental Specifications |
Operating Temperature |
-10°C to +50°C |
Storage Temperature |
-40°C to +60°C |
Operating Humidity |
Non condensing (< 10°C) ≤ 90% RH (at 10°C to 30°C) ≤ 75% RH (at 30°C to 40°C) ≤ 45% RH (at 40°C to 50°C) (Without Condensation) |
Operating Altitude |
2,000 meters |
Storage Altitude |
12,000 meters |
EMI, RFI, EMC, RF |
EN 61326-1:2006, EN 61326-2-2:2006 ETSI EN 300 328 V1.7.1:2006 ETSI EN 300 489 V1.8.1:2008 FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249 FCCID: T68-F381 RSS-210 IC: 6627A-F381 |
Temperature Coefficients |
Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C |
Wireless Frequency |
2.4 GHz ISM Band 10 meter range |
Safety Compliance |
ANSI/ISA S82.02.01:2004 CAN/CSA-C22.2 No. 61010-1-04 IEC/EN 61010-1:2001 to 1000V CAT III, 600V CAT IV. |
Double Insulation Clearance |
Per IEC 6 |